Timbral's calculations draw on a mix of published standards, industry guides, and standard textbook acoustics. This page lists the sources and, in the interest of transparency, records which calculations are implemented from general relationships without a specific document cited in the software. You can also browse the Formula Reference By Standard to see this grouping live.
Standards and guides referenced
| Source | What it covers | Used by |
|---|---|---|
| ISO 9613-2:2024 | Outdoor barrier attenuation (the Dz screening formula, capped at 20 dB) | Barrier — ISO 9613-2 |
| IEC 61672-1:2013 | A- and C-weighting values (tabulated 10 Hz – 10 kHz; the standard's analytic form below 10 Hz) | A-Weighted Total (=DBA); C-Weighted Total (=DBC); A and C in the Weighting Curve Fill |
| ISO 1996-1 / BS 8233:2014 (Annex B) | Noise Rating (NR) curve constants, L = a + b·N. Timbral uses the formula, which disagrees with some values in the printed Annex B table | NR Rating (=NRRATING); NR Curve Fill |
| ProPG Gym Acoustics Guidance 2023 (Appendix G, Table G1) | Gym-noise G-curves (G10–G50) | G-Rating (=GRATING); G Curve Fill |
| ISO 717-1 | Single-number airborne ratings Rw, Dw and DnT,w with the C and Ctr adaptation terms; combining sound reduction indices from 1/3-octave to octave bands | Ratings › Sound Insulation (=SRIRATING); =SRITHIRDTOOCTAVE |
| ISO 11654 | Weighted sound absorption coefficient αw, shape indicators and absorption classes A–E | αw (=ABSORPTIONWEIGHTING); Absorption Class (=ABSORPTIONCLASS); Absorption Class Curve Fill |
| ISO 16283-1 (Formula 14) | Background-noise correction | =BGCORRECT (and its older spelling =BGCORR) |
| ISO 2631-1 | Whole-body vibration frequency weightings (Wb vertical, Wd horizontal) and the estimated vibration dose value | eVDV from Acceleration |
| ISO 226:2003 | Equal-loudness contours | ISO 226 Equal-Loudness Contour Fill |
| ISO 389-7:2019 | Reference hearing threshold (free and diffuse field) | ISO 389-7 Hearing Threshold Fill |
| NS 8178:2014 (Figures 1 and 2) | Reverberation-time limits for music rehearsal and performance rooms | NS 8178 RT Limits |
| BS 8233:2014 (Appendix G) | Outside-to-inside facade level difference (noise break-in) | Outside → Inside (BS 8233) |
| SRL — Noise Control in Building Services | Fan sound-power data (Fig 7.6); unlined-duct attenuation (Fig 7.9); plantroom break-out | Fan Sound Power Level (SRL method); Straight Duct Attenuation (SRL method); Plantroom Louvre; Room Constant |
| CIBSE Guide B4 (2016) | Fan sound power (Formula 4.1, Tables 4.1/4.3); straight duct attenuation (Table 4.19 unlined, Table 4.20 lined); 90° bend attenuation (Tables 4.22/4.23); duct junction attenuation (Formula 4.5); end reflection loss at a flush termination; outlet directivity (Table 4.43) and louvre directivity (Tables 4.43/4.44); crosstalk entering a duct (Formulas 4.29/4.30); rectangular duct breakout (§4.6.10, Formula 4.9, Table 4.30, Figure 4.42) and break-in (Formula 4.12, Tables 4.32/4.33); duct outlet to receiver (Eqs 4.20/4.21, Table 4.42) | Fan Sound Power Level (CIBSE method); Straight Duct Attenuation (CIBSE method, the default); Duct Bend Attenuation (CIBSE); Junction/Split; End Reflection Loss (CIBSE method); Outlet directivity (indoors); Louvre Angle (outdoors); Crosstalk in-duct SWL; Rectangular Duct Breakout; Rectangular Duct Break-in; Outlet to receiver (Internal); the matching elements of a Duct run |
| ASHRAE Handbook 2023 | End reflection loss (a₁ = 0.7, a₂ = 2, capped at 14 dB); ceiling plenum break-out (p 49.39, Table 42 area adjustment) | End Reflection Loss (ASHRAE method); Ceiling Plenum Breakout |
ℹ️ Two further standards underpin definitions rather than calculations: ISO 266 (the standard 1/3-octave band centre frequencies) and ISO 216 (the A-series paper sizes offered when calibrating a PDF by paper size).
Formulae implemented without a cited source
Many of Timbral's calculations are standard, universally-used relationships that the software implements without attributing them to a particular published document. They are no less valid — this note simply records where a specific citation is not present in the code, so you know which figures rest on general acoustics rather than a named standard:
- Fundamentals — speed of sound, wavelength, time correction, number of sources (=SOURCECOUNTCORRECTION) and =RMS.
- Propagation — point / line / plane-source distance attenuation; point / line source power-to-pressure (including the −11 dB and −8 dB free-field constants); conformal and parallelipiped area propagation.
- Reverberation & rooms — Sabine and Eyring reverberation time (RT from Sabines, RT from Alpha) and Sabines from RT (the 0.161 metric constant); Lp,rev from V and RT; SPL in Room (Direct + Reverberant); Schroeder frequency; room mode frequency. The large-room branch of Outlet to receiver (Internal) also uses the general direct-plus-reverberant equation.
- Transmission — inside-to-outside transfer (the −14 dB constant); room-to-room transfer; composite transmission loss; the mass law (the 42 / 48 dB constants).
- Ratings & weightings — the Z-weighted total; the B and D weightings (no longer part of IEC 61672-1); the R and H weightings, which are Timbral's own curves rather than published ones.
- dB and band arithmetic — decibel add / average / subtract; the 1/3→1/1 conversions for levels and absorption (the SRI conversion does cite ISO 717-1).
- Fan tones — blade passage frequency.
- Vibration — static deflection ↔ resonant frequency, and the vibration converter.