Skip to content
ContentsSources & StandardsUser guide

Sources & Standards

Timbral's calculations draw on a mix of published standards, industry guides, and standard textbook acoustics. This page lists the sources and, in the interest of transparency, records which calculations are implemented from general relationships without a specific document cited in the software. You can also browse the Formula Reference By Standard to see this grouping live.

Standards and guides referenced

SourceWhat it coversUsed by
ISO 9613-2:2024Outdoor barrier attenuation (the Dz screening formula, capped at 20 dB)Barrier — ISO 9613-2
IEC 61672-1:2013A- and C-weighting values (tabulated 10 Hz – 10 kHz; the standard's analytic form below 10 Hz)A-Weighted Total (=DBA); C-Weighted Total (=DBC); A and C in the Weighting Curve Fill
ISO 1996-1 / BS 8233:2014 (Annex B)Noise Rating (NR) curve constants, L = a + b·N. Timbral uses the formula, which disagrees with some values in the printed Annex B tableNR Rating (=NRRATING); NR Curve Fill
ProPG Gym Acoustics Guidance 2023 (Appendix G, Table G1)Gym-noise G-curves (G10–G50)G-Rating (=GRATING); G Curve Fill
ISO 717-1Single-number airborne ratings Rw, Dw and DnT,w with the C and Ctr adaptation terms; combining sound reduction indices from 1/3-octave to octave bandsRatings › Sound Insulation (=SRIRATING); =SRITHIRDTOOCTAVE
ISO 11654Weighted sound absorption coefficient αw, shape indicators and absorption classes A–Eαw (=ABSORPTIONWEIGHTING); Absorption Class (=ABSORPTIONCLASS); Absorption Class Curve Fill
ISO 16283-1 (Formula 14)Background-noise correction=BGCORRECT (and its older spelling =BGCORR)
ISO 2631-1Whole-body vibration frequency weightings (Wb vertical, Wd horizontal) and the estimated vibration dose valueeVDV from Acceleration
ISO 226:2003Equal-loudness contoursISO 226 Equal-Loudness Contour Fill
ISO 389-7:2019Reference hearing threshold (free and diffuse field)ISO 389-7 Hearing Threshold Fill
NS 8178:2014 (Figures 1 and 2)Reverberation-time limits for music rehearsal and performance roomsNS 8178 RT Limits
BS 8233:2014 (Appendix G)Outside-to-inside facade level difference (noise break-in)Outside → Inside (BS 8233)
SRL — Noise Control in Building ServicesFan sound-power data (Fig 7.6); unlined-duct attenuation (Fig 7.9); plantroom break-outFan Sound Power Level (SRL method); Straight Duct Attenuation (SRL method); Plantroom Louvre; Room Constant
CIBSE Guide B4 (2016)Fan sound power (Formula 4.1, Tables 4.1/4.3); straight duct attenuation (Table 4.19 unlined, Table 4.20 lined); 90° bend attenuation (Tables 4.22/4.23); duct junction attenuation (Formula 4.5); end reflection loss at a flush termination; outlet directivity (Table 4.43) and louvre directivity (Tables 4.43/4.44); crosstalk entering a duct (Formulas 4.29/4.30); rectangular duct breakout (§4.6.10, Formula 4.9, Table 4.30, Figure 4.42) and break-in (Formula 4.12, Tables 4.32/4.33); duct outlet to receiver (Eqs 4.20/4.21, Table 4.42)Fan Sound Power Level (CIBSE method); Straight Duct Attenuation (CIBSE method, the default); Duct Bend Attenuation (CIBSE); Junction/Split; End Reflection Loss (CIBSE method); Outlet directivity (indoors); Louvre Angle (outdoors); Crosstalk in-duct SWL; Rectangular Duct Breakout; Rectangular Duct Break-in; Outlet to receiver (Internal); the matching elements of a Duct run
ASHRAE Handbook 2023End reflection loss (a₁ = 0.7, a₂ = 2, capped at 14 dB); ceiling plenum break-out (p 49.39, Table 42 area adjustment)End Reflection Loss (ASHRAE method); Ceiling Plenum Breakout

ℹ️ Two further standards underpin definitions rather than calculations: ISO 266 (the standard 1/3-octave band centre frequencies) and ISO 216 (the A-series paper sizes offered when calibrating a PDF by paper size).

Formulae implemented without a cited source

Many of Timbral's calculations are standard, universally-used relationships that the software implements without attributing them to a particular published document. They are no less valid — this note simply records where a specific citation is not present in the code, so you know which figures rest on general acoustics rather than a named standard:

  • Fundamentals — speed of sound, wavelength, time correction, number of sources (=SOURCECOUNTCORRECTION) and =RMS.
  • Propagation — point / line / plane-source distance attenuation; point / line source power-to-pressure (including the −11 dB and −8 dB free-field constants); conformal and parallelipiped area propagation.
  • Reverberation & rooms — Sabine and Eyring reverberation time (RT from Sabines, RT from Alpha) and Sabines from RT (the 0.161 metric constant); Lp,rev from V and RT; SPL in Room (Direct + Reverberant); Schroeder frequency; room mode frequency. The large-room branch of Outlet to receiver (Internal) also uses the general direct-plus-reverberant equation.
  • Transmission — inside-to-outside transfer (the −14 dB constant); room-to-room transfer; composite transmission loss; the mass law (the 42 / 48 dB constants).
  • Ratings & weightings — the Z-weighted total; the B and D weightings (no longer part of IEC 61672-1); the R and H weightings, which are Timbral's own curves rather than published ones.
  • dB and band arithmetic — decibel add / average / subtract; the 1/3→1/1 conversions for levels and absorption (the SRI conversion does cite ISO 717-1).
  • Fan tones — blade passage frequency.
  • Vibration — static deflection ↔ resonant frequency, and the vibration converter.

Register interest