Straight Duct Attenuation

Formula
CIBSE Guide B4 Table 4.19 (unlined), 4.20/4.21 (lined) — dB/m × length; ASHRAE 2023 Tables 16/19 (unlined) + 17/18/20/21 (lining insertion loss)
Output
dB (negative = attenuation)
Bands
63 Hz – 8 kHz (ASHRAE round: 63 Hz – 4 kHz; legacy SRL: 63 Hz – 4 kHz)
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Gives the attenuation of a straight duct run. A Method switch chooses the data source:

  • CIBSE — CIBSE Guide B4's unlined-duct table (4.19). A Lining toggle switches to the lined-duct tables: Table 4.20 for a rectangular duct (25 or 50 mm lining, by the free internal dimension) or Table 4.21 for a circular duct (25 mm lining only, by the free bore).
  • ASHRAE — ASHRAE 2023 Handbook, Chapter 49: unlined attenuation from Table 16 (rectangular) or Table 19 (round); a lined duct adds the lining's insertion loss from Tables 17/18 (rectangular, 25/50 mm) or Tables 20/21 (round).
  • SRL — no longer offered for new blocks. A block saved with the SRL method (natural attenuation of a plain duct) keeps computing exactly as before.

A new block is rectangular, 300 × 300 mm, 1 m long.

Equation

SRL / CIBSE unlined:

A(band)=aper-metre(size, band)×LA(\text{band}) = a_{\text{per-metre}}(\text{size, band}) \times L

SRL's rectangular ducts use the smaller of width and height as the characteristic dimension. CIBSE Table 4.19 looks a rectangular duct's width and height up separately and sums the two per-metre rates (the table's own footnote); its ≥500 Hz rate is held flat to 8 kHz.

CIBSE lined (rectangular only):

A(band)=aper-metre(inner size, lining, band)×LA(\text{band}) = a_{\text{per-metre}}(\text{inner size, lining, band}) \times L

The free internal dimension is the outer dimension minus twice the lining thickness. Capped at −40 dB; returns blank if either inner dimension falls below 100 mm.

CIBSE lined (circular): Table 4.21's per-metre rate for the bore (25 mm lining) × length, total capped at −40 dB.

ASHRAE:

A(band)=aunlined(size, band)×L  +  ILlining(size, thickness, L, band)A(\text{band}) = a_{\text{unlined}}(\text{size, band}) \times L \; + \; IL_{\text{lining}}(\text{size, thickness, } L,\ \text{band})

ℹ️ ASHRAE table lookups. Table 16 is read at the row whose perimeter-to-area ratio 2(W+H)/(W·H) is nearest the duct's (a tie takes the larger duct); Table 19 by diameter range (no extrapolation above 1520 mm; it has no 8 kHz column). For a lined rectangular duct (Tables 17/18) the length is rounded down to whole metres, interpolated linearly between the tabulated lengths and held at the 12 m values beyond 12 m. Tables 17/18 print several rows per size and length without saying what distinguishes them; Timbral takes the lowest insertion loss at each band (worst case). A lined round duct (Tables 20/21) must be a tabulated diameter. ASHRAE dimensions are internal. The ASHRAE total is not capped.

Inputs

InputMeaningUnitMethod
MethodCIBSE or ASHRAE (SRL only on saved blocks)selectall
Duct typecircular or rectangularselectall
Diameter / Width, Heightduct cross-section (CIBSE lined: outer size; ASHRAE: internal size)mmall
Lengthduct run lengthmall
Liningwhether the duct is linedselect (y/n)CIBSE, ASHRAE
Lining thickness25 or 50 mm (shown only when Lining = y; CIBSE circular is 25 mm only)selectCIBSE rectangular, ASHRAE

Worked example — SRL, unlined

Circular Ø300 mm, length 5 m: the block writes the attenuation in each band from 63 Hz to 4 kHz — the per-metre rate for that duct size, which Timbral reads from SRL Figure 7.9, times the 5 m length.

Worked example — CIBSE, lined

Outer 350×200 mm (→ free internal 300×150 mm), 25 mm lining, length 5 m:

Band (Hz)63125250500100020004000
Attenuation (dB)−3.30−8.85−24.25−40−40−40−38.20

(The 500 Hz–2 kHz bands hit the −40 dB cap over this 5 m run.)

Worked example — ASHRAE, rectangular

300 × 300 mm internal, length 5 m. Table 16 row 305 × 305 (nearest P/A); with a 25 mm lining, Table 17 interpolated between its 3 m and 6 m rows (5 m is two thirds of the way):

Band (Hz)631252505001000200040008000
Unlined, Table 16 (dB/m)1.150.660.330.200.200.200.200.20
Unlined × 5 m (dB)−5.75−3.30−1.65−1.00−1.00−1.00−1.00−1.00
Lining IL, Table 17 (dB)0−1.67−7.67−22.67−46.33−29.33−18.67−16.00
Lined total (dB)−5.75−4.97−9.32−23.67−47.33−30.33−19.67−17.00

(e.g. at 1 kHz: 3 m row 39 dB, 6 m row 50 dB → 39 + (50 − 39) × 2/3 = 46.33 dB; total −1.00 − 46.33 = −47.33 dB.)

Source

CIBSE Guide B4 (2016) — Table 4.19 (unlined), Table 4.20 (lined rectangular) and Table 4.21 (lined circular, 25 mm), lined totals capped at −40 dB. ASHRAE 2023 Handbook — HVAC Applications (SI), Chapter 49 — Tables 16 and 19 (unlined rectangular and round), Tables 17/18 and 20/21 (lining insertion loss). Legacy: SRL, Noise Control in Building Services (Figure 7.9, unlined-duct attenuation, 63–4000 Hz).