Skip to content
ContentsFormula ReferenceUser guide
Formula Reference

Rectangular Duct Breakout

Formula
Lw,out = Lw,in − TL + 10·log₁₀(L) − E (CIBSE Guide B4 Formula 4.9, Table 4.30, Figure 4.42)
Output
dB — sound power level radiated by the duct walls (Lw) per band
Bands
63 Hz – 4 kHz
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Estimates the sound power that breaks out through the walls of a rectangular sheet-steel duct as it passes through a room or ceiling void (the "critical area"), per CIBSE Guide B4 Formula 4.9. Takes the in-duct sound power where the duct enters that area, the steel thickness, the duct section and the exposed length.

Equation

Lw,out=Lw,in−TL+10log⁡10(L)−EL_{w,\text{out}} = L_{w,\text{in}} - TL + 10\log_{10}(L) - E
  • TL — breakout transmission loss from CIBSE Table 4.30, by steel thickness and cross-section.
  • E — the additional duct length effect, which stops a long, low-TL duct from radiating more power than it carries. Timbral interpolates it from CIBSE Guide B4 Figure 4.42.

ℹ️ Table lookup. Table 4.30 lists eleven sections (150×150 to 1200×1800 mm). Timbral uses the nearest one, by the summed difference of the two sides in either order; a tie takes the lower TL band by band (the conservative choice, more breakout), and a larger duct takes the largest section.

Inputs

InputMeaningUnitExample
Lw,inin-duct sound power where the duct enters the critical area (a spectrum row)dBsee below
Steel duct thickness0.7 (22 swg), 0.9 (20 swg), 1.2 (18 swg) or 1.6 (16 swg)mm0.7 (22 swg)
Width, Heightduct cross-section (must be greater than 0)mm300 × 300
Lexposed duct length inside the critical aream5

Worked example

0.7 mm (22 swg) steel, 300 × 300 mm, L = 5 m (10·log₁₀L = 6.99 dB):

Band (Hz)63125250500100020004000
Lw,in (dB)80787470656055
TL (dB)13181920232630
E (dB)0.600.350.320.300.250.210.17
Lw,out (dB)73.466.661.756.748.740.831.8

(e.g. at 63 Hz: 80 − 13 + 6.99 − 0.60 = 73.4 dB.)

Source

CIBSE Guide B4 (2016) — Formula 4.9 (duct breakout), Table 4.30 (breakout transmission loss of rectangular ducts) and Figure 4.42 (additional duct length effect). Bands 63–4000 Hz.