Rectangular Duct Break-in

Formula
Lw = SPLin + Δ − Tlin + 10·log₁₀(S) (CIBSE Guide B4 Formula 4.12, Tables 4.33 and 4.32)
Output
dB — sound power level entering the duct (Lw) per band
Bands
63 Hz – 8 kHz
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Estimates the sound power that breaks into a rectangular sheet-steel duct through its walls from the reverberant sound field of the room it passes through, per CIBSE Guide B4 Formula 4.12 — e.g. plantroom noise getting into a duct that then carries it elsewhere.

Equation

Lw=SPLin+Δ−TLin+10log⁡10(S)L_w = SPL_{in} + \Delta - TL_{in} + 10\log_{10}(S)
  • SPLin — the reverberant sound pressure level incident on the duct wall.
  • Δ — the Table 4.32 low-frequency correction for the room surfaces next to the duct: 1 surface +3, +2, +1 dB; 2 surfaces +6, +4, +2 dB at 63, 125, 250 Hz; 0 dB above.
  • Tlin — break-in transmission loss from CIBSE Table 4.33, by steel thickness and cross-section.
  • S — the duct's cross-sectional area, width × height, in m².

ℹ️ Table lookup. Table 4.33 uses the same eleven sections as the breakout table (150×150 to 1200×1800 mm). Timbral uses the nearest one, by the summed difference of the two sides in either order; a tie takes the lower Tlin band by band, and a larger duct takes the 1200 × 1800 values.

Inputs

InputMeaningUnitExample
SPLinincident reverberant SPL on the duct wall (a spectrum row)dBsee below
Steel duct thickness0.7 (22 swg), 0.9 (20 swg), 1.2 (18 swg) or 1.6 (16 swg)mm0.7 (22 swg)
Width, Heightduct cross-section (must be greater than 0)mm300 × 300
Reflecting surfaces by ductnumber of room surfaces adjacent to the duct: 1 or 2—1

Worked example

0.7 mm (22 swg) steel, 300 × 300 mm (S = 0.09 m², 10·log₁₀S = −10.46 dB), 1 reflecting surface:

Band (Hz)631252505001000200040008000
SPLin (dB)8078747065605550
Δ (dB)+3+2+100000
Tlin (dB)1414172631343942
Lw (dB)58.555.547.533.523.515.55.5−2.5

(e.g. at 63 Hz: 80 + 3 − 14 − 10.46 = 58.5 dB.)

Source

CIBSE Guide B4 (2016) — Formula 4.12 (duct break-in), Table 4.33 (break-in transmission loss of rectangular ducts) and Table 4.32 (correction for reflecting surfaces). Bands 63–8000 Hz.