- Formula
- Lw = SPLin + Δ − Tlin + 10·log₁₀(S) (CIBSE Guide B4 Formula 4.12, Tables 4.33 and 4.32)
- Output
- dB — sound power level entering the duct (Lw) per band
- Bands
- 63 Hz – 8 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Estimates the sound power that breaks into a rectangular sheet-steel duct through its walls from the reverberant sound field of the room it passes through, per CIBSE Guide B4 Formula 4.12 — e.g. plantroom noise getting into a duct that then carries it elsewhere.
Equation
- SPLin — the reverberant sound pressure level incident on the duct wall.
- Δ — the Table 4.32 low-frequency correction for the room surfaces next to the duct: 1 surface +3, +2, +1 dB; 2 surfaces +6, +4, +2 dB at 63, 125, 250 Hz; 0 dB above.
- Tlin — break-in transmission loss from CIBSE Table 4.33, by steel thickness and cross-section.
- S — the duct's cross-sectional area, width × height, in m².
ℹ️ Table lookup. Table 4.33 uses the same eleven sections as the breakout table (150×150 to 1200×1800 mm). Timbral uses the nearest one, by the summed difference of the two sides in either order; a tie takes the lower Tlin band by band, and a larger duct takes the 1200 × 1800 values.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| SPLin | incident reverberant SPL on the duct wall (a spectrum row) | dB | see below |
| Steel duct thickness | 0.7 (22 swg), 0.9 (20 swg), 1.2 (18 swg) or 1.6 (16 swg) | mm | 0.7 (22 swg) |
| Width, Height | duct cross-section (must be greater than 0) | mm | 300 × 300 |
| Reflecting surfaces by duct | number of room surfaces adjacent to the duct: 1 or 2 | — | 1 |
Worked example
0.7 mm (22 swg) steel, 300 × 300 mm (S = 0.09 m², 10·log₁₀S = −10.46 dB), 1 reflecting surface:
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|
| SPLin (dB) | 80 | 78 | 74 | 70 | 65 | 60 | 55 | 50 |
| Δ (dB) | +3 | +2 | +1 | 0 | 0 | 0 | 0 | 0 |
| Tlin (dB) | 14 | 14 | 17 | 26 | 31 | 34 | 39 | 42 |
| Lw (dB) | 58.5 | 55.5 | 47.5 | 33.5 | 23.5 | 15.5 | 5.5 | −2.5 |
(e.g. at 63 Hz: 80 + 3 − 14 − 10.46 = 58.5 dB.)
Source
CIBSE Guide B4 (2016) — Formula 4.12 (duct break-in), Table 4.33 (break-in transmission loss of rectangular ducts) and Table 4.32 (correction for reflecting surfaces). Bands 63–8000 Hz.