Skip to content
ContentsFormula ReferenceUser guide
Formula Reference

Plantroom Louvre

Formula
Lw = Lp + 10·log₁₀(S) − 6
Output
dB — sound power level (Lw) per band
Bands
Follows the input spectrum
Standard / Source
SRL — Noise Control in Building Services
Access
Toolbar block

What it does

Converts the reverberant sound pressure level inside a plantroom into the sound power level radiated out through a louvre of area S — the first step in predicting plantroom break-out noise at neighbouring properties.

Equation

Lw=Lp+10 log⁡10(S)−6L_w = L_p + 10\,\log_{10}(S) - 6

where S is the louvre's open area (width × height).

Inputs

InputMeaningUnitExample
Lpreverberant SPL in the plantroom (a spectrum row)dBsee below
Widthlouvre widthm1
Heightlouvre heightm1

Worked example

Louvre 1 × 1 m (S = 1 m², so the offset is 10·log₁₀(1) − 6 = −6 dB), with plantroom Lₚ as shown:

Band (Hz)631252505001000200040008000
Lp in (dB)9092888582807875
Lw out (dB)8486827976747269

Source

SRL, Noise Control in Building Services.