- Formula
- D = Rc + 10·log₁₀(S / A) + 3 + contingency
- Output
- dB — two rows per band: Transfer Function (level difference D, negative) and Predicted internal SPL
- Bands
- Follows the input spectrum
- Standard / Source
- BS 8233:2014 App G
- Access
- Toolbar block
What it does
Computes the outside-to-inside level difference across a facade, following the break-in method of BS 8233:2014 Appendix G. It takes the facade's composite transmission loss Rc as one spectrum row — work that out first with Composite Transmission Loss (which combines the wall build-ups, glazing and vents by area), then copy its values into this block or bind the input to its published variable — and combines it with the facade area, the receiving-room absorption and a user contingency. Ribbon: Buildings → Outside → Inside (BS 8233).
The block has two result rows: the Transfer Function (the level difference D) and, below it, the Predicted SPL inside, filled only when a free-field external spectrum is given.
Equation
where Rc is the facade's composite transmission loss (negative), S the facade area it describes, A the receiving-room absorption (derived per band as A = 0.161·V / T₆₀) and +3 dB the Appendix G facade correction. If a free-field spectrum is supplied, the Predicted SPL row gives the inside level Leq₂ = Leq,ff + D.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Leq,ff | free-field external SPL (a spectrum row; optional) | dB | 65 |
| Rc | composite transmission loss (a spectrum row, negative) | dB | see below |
| S | facade area | m² | 10 |
| V | receiving-room volume | m³ | 35 |
| T₆₀ | receiving-room reverberation time (a spectrum row) | s | 0.5 |
| Contingency | margin added to the level difference (shown across the bands) | dB | 2 |
Worked example
The wall + door composite from the Composite Transmission Loss example, S = 10 m², a receiving room of V = 35 m³ with T₆₀ = 0.5 s (so A = 0.161 × 35 / 0.5 = 11.27 m² and 10·log₁₀(S/A) = −0.52 dB), 2 dB contingency, and a free-field level of 65 dB in every band:
| Band (Hz) | 125 | 250 | 500 | 1000 |
|---|---|---|---|---|
| Rc (dB) | −25.65 | −26.67 | −27.71 | −32.71 |
| D — Transfer Function (dB) | −21.17 | −22.19 | −23.23 | −28.23 |
| Predicted SPL (dB) | 43.83 | 42.81 | 41.77 | 36.77 |
(e.g. at 500 Hz: −27.71 − 0.52 + 3 + 2 = −23.23 dB; 65 − 23.23 = 41.77 dB.)
ℹ️ Blocks saved before v0.5.0 used an older form of this calc that built the composite itself from a range of element rows (with vents entered as type “Dn,e”). They still recalculate exactly as before; newly inserted blocks use the composite-TL form above.
Source
BS 8233:2014, Appendix G — outside-to-inside facade level difference (noise break-in).