Outside → Inside — Facade Attenuation (BS 8233:2014 Appendix G)

Formula
D = Rc + 10·log₁₀(S / A) + 3 + contingency
Output
dB — two rows per band: Transfer Function (level difference D, negative) and Predicted internal SPL
Bands
Follows the input spectrum
Standard / Source
BS 8233:2014 App G
Access
Toolbar block

What it does

Computes the outside-to-inside level difference across a facade, following the break-in method of BS 8233:2014 Appendix G. It takes the facade's composite transmission loss Rc as one spectrum row — work that out first with Composite Transmission Loss (which combines the wall build-ups, glazing and vents by area), then copy its values into this block or bind the input to its published variable — and combines it with the facade area, the receiving-room absorption and a user contingency. Ribbon: Buildings → Outside → Inside (BS 8233).

The block has two result rows: the Transfer Function (the level difference D) and, below it, the Predicted SPL inside, filled only when a free-field external spectrum is given.

Equation

D=Rc+10 log⁡10 ⁣(SA)+3+contingencyD = R_c + 10\,\log_{10}\!\left(\frac{S}{A}\right) + 3 + \text{contingency}

where Rc is the facade's composite transmission loss (negative), S the facade area it describes, A the receiving-room absorption (derived per band as A = 0.161·V / T₆₀) and +3 dB the Appendix G facade correction. If a free-field spectrum is supplied, the Predicted SPL row gives the inside level Leq₂ = Leq,ff + D.

Inputs

InputMeaningUnitExample
Leq,fffree-field external SPL (a spectrum row; optional)dB65
Rccomposite transmission loss (a spectrum row, negative)dBsee below
Sfacade aream²10
Vreceiving-room volumem³35
T₆₀receiving-room reverberation time (a spectrum row)s0.5
Contingencymargin added to the level difference (shown across the bands)dB2

Worked example

The wall + door composite from the Composite Transmission Loss example, S = 10 m², a receiving room of V = 35 m³ with T₆₀ = 0.5 s (so A = 0.161 × 35 / 0.5 = 11.27 m² and 10·log₁₀(S/A) = −0.52 dB), 2 dB contingency, and a free-field level of 65 dB in every band:

Band (Hz)1252505001000
Rc (dB)−25.65−26.67−27.71−32.71
D — Transfer Function (dB)−21.17−22.19−23.23−28.23
Predicted SPL (dB)43.8342.8141.7736.77

(e.g. at 500 Hz: −27.71 − 0.52 + 3 + 2 = −23.23 dB; 65 − 23.23 = 41.77 dB.)

ℹ️ Blocks saved before v0.5.0 used an older form of this calc that built the composite itself from a range of element rows (with vents entered as type “Dn,e”). They still recalculate exactly as before; newly inserted blocks use the composite-TL form above.

Source

BS 8233:2014, Appendix G — outside-to-inside facade level difference (noise break-in).