Outlet to receiver (Direct + Reverberant, from RT)

Formula
Lp = 10·lg(10^(Lp,D/10) + 10^(Lp,R/10)); Lp,D = Lw + D1 + D2; Lp,R = Lw + 10·lg(4/R) (CIBSE Guide B4 Eqs 4.14–4.18, 4.23, Table 4.43)
Output
dB — sound pressure level at the receiver, per band
Bands
63 Hz – 8 kHz
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Predicts the sound pressure level at a listener from a single duct outlet (a grille or diffuser) in a room, as the sum of the direct sound and the reverberant sound. Instead of a room constant you supply, the room's absorption comes from its measured or predicted reverberation time and its dimensions (Sabine). For the method that takes a room constant directly, see Outlet to receiver (Internal).

Equation

Lp=10log⁡10(10Lp,D/10+10Lp,R/10)L_p = 10\log_{10}\left(10^{L_{p,D}/10} + 10^{L_{p,R}/10}\right)

Direct sound:

Lp,D=Lw+D1+D2,D1=−(20log⁡10r+11)L_{p,D} = L_w + D_1 + D_2,\qquad D_1 = -(20\log_{10} r + 11)

Reverberant sound:

Lp,R=Lw+10log⁡104R,R=A1−αˉ,αˉ=AS,A=0.161 VTL_{p,R} = L_w + 10\log_{10}\frac{4}{R},\qquad R = \frac{A}{1-\bar\alpha},\qquad \bar\alpha = \frac{A}{S},\qquad A = \frac{0.161\,V}{T}
  • D2 — the outlet's directivity from CIBSE Table 4.43, by mounting position and outlet area, applied to the direct sound only. 63 Hz takes the 125 Hz value; the area rounds down to a tabulated row (0.01, 0.05, 0.1, 0.25, 1 or 10 m²; below 0.01 m² uses the 0.01 m² row). A free-space outlet has D2 = 0.
  • V, S — room volume and total surface area, from its length, width and height.

ℹ️ A band with no reverberation time has no result, and so does a band where T ≤ 0.161·V/S (the mean absorption coefficient would reach 1). The workings also flag a small room (V < 425 m³, where a reverberant field may not form), a long flat room, a listener in the outlet's near field (when you give its largest dimension) and a room dead enough that the Schultz method is usually preferred.

Inputs

InputMeaningUnitExample
Lwoutlet sound power (a spectrum row; the bare source Lw)dBsee below
Treverberation time of the room (a spectrum row)ssee below
L, W, Hroom length, width and heightm6 × 5 × 3
rdistance from the outlet to the listenerm2
Mounting positionA = flush in one surface; B = at the junction of two surfaces; C = in a corner of three; Free space—A
Outlet areaselects the Table 4.43 row (positions A and B)m²0.05
Largest outlet dimension (optional)used only for the near-field checkm0.25

Worked example

Room 6 × 5 × 3 m (V = 90 m³, S = 126 m²), r = 2 m (D1 = −17.0 dB), position A, 0.05 m² outlet:

Band (Hz)631252505001000200040008000
Lw (dB)7068656260575450
T (s)1.00.90.80.70.70.60.60.5
D2 (dB)44567889
Lp (dB)64.762.359.055.854.251.148.144.2

At 1 kHz: Lp,D = 60 − 17.02 + 7 = 49.98 dB; A = 0.161 × 90 / 0.7 = 20.7 m², ᾱ = 20.7/126 = 0.164, R = 20.7/(1 − 0.164) = 24.8 m², Lp,R = 60 + 10·log₁₀(4/24.8) = 52.08 dB; Lp = 10·log₁₀(10^4.998 + 10^5.208) = 54.2 dB.

Source

CIBSE Guide B4 (2016) — Equations 4.14–4.18 and 4.23 (direct and reverberant sound from an outlet) and Table 4.43 (outlet directivity). The absorption area A comes from the reverberation time by Sabine's formula. Bands 63–8000 Hz.