Skip to content
ContentsFormula ReferenceUser guide
Formula Reference

Lp,rev from V and RT (Reverberant SPL)

Formula
Lp,rev = Lw − 10·log₁₀(V) + 10·log₁₀(RT) + 14 + 10·log₁₀(N)
Output
dB — reverberant SPL per band
Bands
Follows the input spectra
Standard / Source
General acoustics (no standard cited)
Access
Toolbar block

What it does

Estimates the reverberant-field sound pressure level in a room produced by one or more sources of known sound power, given the room volume and reverberation time. This is the diffuse-field level away from any single source, e.g. the general level inside a plantroom. Ribbon: Buildings → Lp,rev from V and RT.

Equation

Lp,rev=Lw−10 log⁡10(V)+10 log⁡10(RT)+14+10 log⁡10(N)L_{p,rev} = L_w - 10\,\log_{10}(V) + 10\,\log_{10}(\text{RT}) + 14 + 10\,\log_{10}(N)

with V the room volume, RT the reverberation time (per band), and N the number of identical sources. A band whose RT is blank or zero is left blank.

Inputs

InputMeaningUnitExample
Lwsource sound power level (a spectrum row)dB90
RTreverberation time (a spectrum row)s0.75
Vroom volumem³200
Nnumber of sources—1

Worked example

At 63 Hz — Lw = 90 dB, RT = 0.75 s, V = 200 m³, N = 1:

90−10 log⁡10(200)+10 log⁡10(0.75)+14+0=90−23.01−1.25+14=79.7 dB90 - 10\,\log_{10}(200) + 10\,\log_{10}(0.75) + 14 + 0 = 90 - 23.01 - 1.25 + 14 = \mathbf{79.7\ dB}

Source

Standard diffuse-field (reverberant) level relation. No specific published standard is cited in the software.