Skip to content
ContentsFormula ReferenceUser guide
Formula Reference

Louvre Angle (outdoors)

Formula
CIBSE Guide B4 Tables 4.43 + 4.44 — angle-dependent
Output
dB — directivity correction (floored at −30 dB)
Bands
125 Hz – 8 kHz
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Gives the angle-dependent directivity of an outdoor louvre. It takes the position-A directivity index from Table 4.43 and applies an angle correction from Table 4.44 for the receiver's bearing off the louvre axis, interpolated by angle and floored at −30 dB. At 0° (straight ahead) it equals the indoor position-A value; off-axis it falls away sharply.

Inputs

InputMeaningUnitExample
Outlet area Sfree area of the outletm²0.1
Angle θbearing off the louvre axis°0

Worked example

S = 0.1 m², angle 0° (on-axis) — equals the indoor position-A result:

Band (Hz)1252505001000200040008000
DI (dB)4678999

At a large off-axis angle the corrections become strongly negative (down to the −30 dB floor).

Source

CIBSE Guide B4, Tables 4.43 + 4.44 — position-A directivity index plus angle correction. Bands 125–8000 Hz.