Skip to content
ContentsFormula ReferenceUser guide
Formula Reference

Lined Flexible Duct

Formula
Insertion loss from ASHRAE 2023 Table 25 by nominal diameter and length
Output
dB (negative = attenuation)
Bands
63 Hz – 4 kHz (Table 25 has no 8 kHz column)
Standard / Source
ASHRAE 2023
Access
Toolbar block

What it does

Gives the insertion loss of a lined (non-metallic, insulated) flexible duct, read from ASHRAE 2023 Handbook — HVAC Applications, Chapter 49, Table 25, by its nominal diameter and length. It is also available as an element of a Duct run.

Equation

IL=− ILTable 25(D, L)IL = -\,IL_{\text{Table 25}}(D,\ L)

Timbral writes the loss negative (an attenuation), like every other duct element.

ℹ️ Table lookup. Table 25 lists ten nominal diameters (100, 125, 150, 175, 200, 225, 250, 300, 350 and 400 mm) and four lengths (0.9, 1.8, 2.7 and 3.7 m). Any other diameter gives N/A: Timbral does not interpolate between sizes. For the length, Timbral reads a tabulated length directly, interpolates linearly between two tabulated lengths, scales the 0.9 m row by L/0.9 below 0.9 m, and holds the 3.7 m row above 3.7 m (no extrapolation). The 63 Hz column is ASHRAE's own estimate. Table 25 has no 8 kHz column, so 8 kHz is blank (and a duct run containing one has a blank 8 kHz total).

Inputs

InputMeaningUnitExample
Flexible duct diameterone of Table 25's ten nominal diametersmm200
Flexible duct lengthlength of the flexible duct (must be greater than 0)m2.0

Worked example

D = 200 mm, L = 2.0 m, between the 1.8 m and 2.7 m rows (fraction (2.0 − 1.8)/(2.7 − 1.8) = 0.222):

Band (Hz)63125250500100020004000
Table 25, 1.8 m (dB)461117191912
Table 25, 2.7 m (dB)681625282818
Result (dB)−4.4−6.4−12.1−18.8−21.0−21.0−13.3

(e.g. at 500 Hz: 17 + 0.222 × (25 − 17) = 18.8, written as −18.8 dB.)

Source

ASHRAE 2023 Handbook — HVAC Applications (SI), Chapter 49, Table 25 (insertion loss of lined flexible duct). Bands 63–4000 Hz.

Register interest

Tell us a little about you and we'll be in touch when Timbral is ready.