- Formula
- SRL: Lw = 10·log₁₀(Q) + 20·log₁₀(P) + 40 + correction; CIBSE: Lw = Lws + 10·log₁₀(Q) + 20·log₁₀(P) + 40 + BFI + C
- Output
- dB — sound power level (Lw) per band
- Bands
- 63 Hz – 4 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Estimates a fan's sound power level spectrum from its duty (flow and static pressure). A Method switch chooses between two independent models:
- SRL — the simpler of the two: a base level from Q and P, shaped by a per-band spectrum correction characteristic of the fan type (forward/backward-curved centrifugal, axial, mixed-flow).
- CIBSE — CIBSE Guide B4 (2016) Formula 4.1, a more detailed method: the same base level, plus a per-band spectrum correction (and blade-frequency increment) from Table 4.1 for the fan type and wheel size, plus an operating-duty correction from Table 4.3 for how far off its peak-efficiency point the fan runs.
Switching Method changes which inputs the block asks for.
Equation
SRL:
CIBSE:
- Lws — Table 4.1 spectrum correction for the fan type (and, for some types, wheel-size bucket).
- BFI — the Table 4.1 blade-frequency increment, added only to the single octave band that contains the blade-passage frequency BPF = (rpm/60) × blade count.
- C — Table 4.3 operating-duty correction, from the fan's off-peak static efficiency: 90–100% → 0 dB, 85–89% → 3, 75–84% → 6, 65–74% → 9, 55–64% → 12, 50–54% → 15 (below 50%, Table 4.3 is undefined and no correction is applied).
ℹ️ Wheel size only matters for some fan types. Table 4.1 splits by wheel size for "Centrifugal: aerofoil/backward curved" (>900 mm vs ≤900 mm), "Pressure blower" (<500 mm vs ≥500 mm), and "Vaneaxial"/"Tubeaxial" (>1000 mm vs ≤1000 mm). "Centrifugal: forward curved", "Centrifugal: radial blade" and "Propeller (cooling tower)" use one row regardless of the wheel-size value entered.
Inputs
| Input | Meaning | Unit | Method |
|---|---|---|---|
| Method | SRL or CIBSE | select | both |
| Q | volume flow rate | m³/s | both |
| P | fan static pressure | N/m² | both |
| Fan type | forward/backward-curved, axial, mixed | select | SRL |
| Fan type | one of the 7 CIBSE Table 4.1 types | select | CIBSE |
| Wheel size | fan wheel diameter (selects Table 4.1 size bucket where applicable) | mm | CIBSE |
| Operating duty | off-peak static efficiency (selects C from Table 4.3) | % | CIBSE |
| Fan speed | rpm | rpm | CIBSE |
| Blades | number of impeller blades | — | CIBSE |
Worked example — SRL
Q = 2 m³/s, P = 500 N/m², forward-curved centrifugal: the block writes Lw in each band from 63 Hz to 4 kHz — the base level from Q and P plus the forward-curved spectrum correction, which Timbral reads from SRL Figure 7.6.
ℹ️ The SRL source data only spans 63 Hz–4 kHz, so no 31.5 Hz or 8 kHz value is produced.
Worked example — CIBSE
Q = 2 m³/s, P = 500 N/m² (base Lw = 96.99 dB), Centrifugal: forward curved, 900 rpm, 12 blades (BPF = 180 Hz → falls in the 250 Hz band, BFI = +2 dB there), 90% operating duty (C = 0 dB):
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 |
|---|---|---|---|---|---|---|---|
| Lw (dB) | 88.99 | 84.99 | 84.99 | 74.99 | 69.99 | 66.99 | 64.99 |
(250 Hz would otherwise be 82.99 dB before the +2 dB BFI is added, landing it level with 125 Hz.)
Source
SRL, Noise Control in Building Services — fan sound-power data (Figure 7.6), or CIBSE Guide B4 (2016), Formula 4.1 — fan sound power level, with spectrum corrections and blade-frequency increment from Table 4.1 and operating-duty correction from Table 4.3. Both cover 63–4000 Hz.