End Reflection Loss

Formula
CIBSE: ∆Lr = −10·log₁₀[1+(0.8λ/πd)^1.88] (grille/swirl) or ERL = −10·log₁₀(1/T) (slot); ASHRAE: ERL = −10·log₁₀[1+(a₁·c₀/πfD)^a₂]
Output
dB (negative = attenuation)
Bands
63 Hz – 8 kHz (0 dB at ≥2 kHz on CIBSE grille/swirl; flat on slot)
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Gives the end reflection loss at a duct termination (e.g. a grille discharging into a room). Where a duct opens abruptly into a much larger space, low-frequency energy is partly reflected back down the duct instead of radiating out — an effective low-frequency attenuation that fades to nothing at high frequency.

A Method switch chooses the model:

  • CIBSE — Guide B4 (2016), flush termination. A Diffuser type toggle further splits this into grille/swirl (diameter-based) or slot (area-ratio-based).
  • ASHRAE — the 2023 ASHRAE Handbook relation, for blade, grille or slot diffusers (slot again uses the area-ratio form).

Equation

CIBSE, grille/swirl:

ΔLr=−10 log⁡10 ⁣[1+(0.8 λπd)1.88],λ=343f\Delta L_r = -10\,\log_{10}\!\left[1 + \left(\frac{0.8\,\lambda}{\pi d}\right)^{1.88}\right],\qquad \lambda = \frac{343}{f}

Rectangular terminations use an equivalent diameter d=4wh/πd = \sqrt{4wh/\pi}. The loss is taken as 0 dB at 2 kHz and above.

CIBSE or ASHRAE, slot:

ERL=−10 log⁡10 ⁣(1T),T=4 S1S2(S1+S2)2\text{ERL} = -10\,\log_{10}\!\left(\frac{1}{T}\right),\qquad T = \frac{4\,S_1 S_2}{(S_1+S_2)^2}

Frequency-flat — the same value at every band.

ASHRAE, blade/grille:

ERL=−10 log⁡10 ⁣[1+(a1c0πfD)a2]\text{ERL} = -10\,\log_{10}\!\left[1 + \left(\frac{a_1 c_0}{\pi f D}\right)^{a_2}\right]

with a₁ = 0.7 (ducted termination), a₂ = 2, c₀ = 343 m/s. Capped at −14 dB.

Inputs

InputMeaningUnitMethod / type
MethodCIBSE or ASHRAEselectboth
Diffuser typegrille-swirl or slot (CIBSE); blade, grille or slot (ASHRAE)selectboth
Duct type, Diameter / Width×Heightduct or grille cross-sectionmmCIBSE, grille-swirl
S1, S2upstream duct area, diffuser outlet area (defaults 0.036 / 0.0061 m² on CIBSE, 0.045 / 0.0056 m² on ASHRAE)m²slot (either method)
Effective duct diameterDmASHRAE, blade/grille

ℹ️ New blocks and switching. A new block starts CIBSE, grille/swirl, rectangular 450 × 300 mm. When you switch Diffuser type or Method and back, the rows that disappeared come back with the values they held: a rectangular 600 × 400 mm termination switched to slot and back is rectangular 600 × 400 mm again. Where a size has never been entered, it is carried over from the one you have: a circular Diameter takes the width; ASHRAE's effective diameter takes the CIBSE diameter, or √(4wh/π) for a rectangle, to the millimetre; a CIBSE Diameter revealed from ASHRAE takes D. A block saved without a Duct type row reads as circular, exactly as before. Each switch is a single undo step.

Worked example — CIBSE, grille/swirl

Circular Ø450 mm termination:

Band (Hz)631252505001000200040008000
ΔLr (dB)−9.68−5.17−2.10−0.68−0.19000

The effect is strongly low-frequency: nearly 10 dB at 63 Hz, negligible by 1 kHz.

Worked example — CIBSE or ASHRAE, slot

S1 = 0.036 m², S2 = 0.0061 m²:

T = 4(0.036)(0.0061)/(0.0421)² = 0.496 → ERL = −10·log₁₀(1/0.496) = −3.05 dB, applied equally across every band.

Worked example — ASHRAE, blade

Blade diffuser, D = 0.276 m, ducted (a₁ = 0.7):

Band (Hz)631252505001000200040008000
ERL (dB)−13.08−7.71−3.48−1.16−0.32−0.08−0.02−0.01

Source

CIBSE Guide B4 (2016) — end reflection loss, no loss assumed at 2000 Hz and above (grille/swirl); slot diffuser relation. ASHRAE, 2023 ASHRAE Handbook — HVAC Applications, Chapter 49 (Sound and Vibration Control) — end reflection loss relation (blade/grille) and slot diffuser relation.