- Formula
- CIBSE Guide B4 Tables 4.22 / 4.23 (square) and 4.24 (round), or ASHRAE 2023 Tables 22 / 23 (square, radiused) — 90° elbow by f×w, × number of bends
- Output
- dB (negative = attenuation)
- Bands
- 63 Hz – 8 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Gives the attenuation of a 90° bend (elbow) in a duct. Each band's loss is read from a table keyed on the product of frequency and duct width (f×w). A Method switch chooses the data source and an Elbow type switch the shape:
- CIBSE — Guide B4 (2016): square elbows from Table 4.22 (no turning vanes) or Table 4.23 (with vanes), unlined or lined; round elbows from Table 4.24. A 50 mm lining adds 3 dB to the 25 mm figures, except at 63 Hz (§4.6.4.2).
- ASHRAE — 2023 Handbook, Chapter 49: square elbows without turning vanes from Table 22, radiused rectangular elbows from Table 23 (unlined). ASHRAE has no round elbow, so a round elbow on the ASHRAE method shows N/A and asks for CIBSE; square elbows with turning vanes (ASHRAE Table 24) give no result.
A block saved before the Method and Elbow type switches existed reads as CIBSE, square, exactly as before. In a Duct run, a bend after a round element starts as a round CIBSE elbow, even in an ASHRAE run.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Method | CIBSE or ASHRAE | select | CIBSE |
| Elbow type | square, round (CIBSE) or radiused (ASHRAE) | select | square |
| Width | duct dimension in the plane of the bend; for a round elbow the bore (inside any lining) | mm | 300 |
| Turning vanes | fitted? (square elbows) | yes/no | no |
| Lined | acoustically lined? It should run at least two duct widths before and after the bend | yes/no | no |
| Lining thickness | 25 or 50 mm (when lined) | mm | 25 |
| Number of bends | whole number of identical bends; the per-bend attenuation is multiplied by this | — | 1 |
Worked example
Width 300 mm, no vanes, unlined:
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|
| Attenuation (dB) | 0 | 0 | −1 | −5 | −8 | −4 | −3 | −3 |
Most of the loss lands in the mid bands, where the acoustic wavelength is comparable to the duct width. ASHRAE Table 22 gives the same figures for this case.
The same 300 mm duct as a round elbow (CIBSE Table 4.24, f×w < 25 → 0 dB; 25–50 → 1 dB; 50–100 → 2 dB; above 100 → 3 dB), or a radiused elbow (ASHRAE Table 23):
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|
| f×w (kHz·mm) | 18.9 | 37.5 | 75 | 150 | 300 | 600 | 1200 | 2400 |
| Round, CIBSE 4.24 (dB) | 0 | −1 | −2 | −3 | −3 | −3 | −3 | −3 |
| Radiused, ASHRAE 23 (dB) | 0 | 0 | −1 | −2 | −3 | −3 | −3 | −3 |
Source
CIBSE Guide B4 (2016), Tables 4.22 (no vanes) / 4.23 (with vanes) — 90° square elbows, Table 4.24 — round elbows, and §4.6.4.2 (lining thickness), based on the f×w product. ASHRAE 2023 Handbook — HVAC Applications (SI), Chapter 49, Tables 22 and 23 (square and radiused rectangular elbows). Bands 63–8000 Hz.