- Formula
- Lp = Lw − 10·log₁₀(S/S₀); S = (A+B)(2C+πr) + 2πr(C+r) + AB
- Output
- dB — attenuation correction, same value in every band
- Bands
- 31.5 Hz – 8 kHz (same value in every band)
- Standard / Source
- General acoustics (no standard cited)
- Access
- Toolbar block
What it does
Estimates propagation loss from a rectangular plant item (e.g. a chiller or AHU casing) treated as a conformal surface wrapped around the source at distance r — a near-field area-propagation model that sits between a simple point source and a full parallelipiped enclosure model.
Equation
where
and S₀ = 1 m².
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| A | source length | m | 3.6 |
| B | source width | m | 2.5 |
| C | source height | m | 1.7 |
| r | distance of propagation | m | 10 |
Worked example
A = 3.6 m, B = 2.5 m, C = 1.7 m, r = 10 m:
S = (6.1)(3.4 + 31.42) + 2π(10)(11.7) + 9 = 956.5 m²
Correction = −10·log₁₀(956.5) = −29.8 dB, applied equally to every band.
Source
General area-propagation relation for plant enclosures. No specific published standard is cited in the software.