- Formula
- L_room = Lw − EnvAdj(band) − AreaAdj(S, band) − CeilingAtten(type, band)
- Output
- dB — room SPL from plenum breakout, per band
- Bands
- 63 Hz – 4 kHz
- Standard / Source
- ASHRAE 2023
- Access
- Toolbar block
What it does
Predicts the sound pressure level radiated into a room from a return-air plenum above a suspended ceiling — sound that breaks out of ductwork or diffusers into the plenum, then transmits down through the ceiling tiles into the occupied space below. Combines the plenum's radiated sound power with an environmental adjustment, a source-area adjustment, and the chosen ceiling type's own sound attenuation.
Equation
EnvAdj is a fixed per-band environmental adjustment (4, 2, 1 dB at 63/125/250 Hz, 0 dB above); CeilingAtten is read from tabulated per-band data for the selected ceiling construction; AreaAdj is a small correction for the source's radiating area (non-zero only at 63/125/250 Hz, from ASHRAE Table 42; a source area exactly on a row boundary takes the later row).
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Lw | plenum-radiated sound power (a spectrum row) | dB | see below |
| S | source area | m² | 1.3 |
| Ceiling type | construction (select, from ASHRAE table) | — | 16mm mineral fibre 2.4 kg/m² |
Worked example
S = 1.3 m², ceiling = 16mm mineral fibre 2.4 kg/m²:
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 |
|---|---|---|---|---|---|---|---|
| Lw (dB) | 70 | 68 | 65 | 62 | 58 | 54 | 50 |
| L_room (dB) | 51 | 49 | 46 | 43 | 33 | 24 | 17 |
(e.g. at 63 Hz: 70 − 4 (env) − 2 (area) − 13 (ceiling) = 51 dB.)
Source
ASHRAE, 2023 ASHRAE Handbook — HVAC Applications, Chapter 49 (Sound and Vibration Control), p49.39 — plenum breakout through a suspended ceiling.