- Formula
- La = Lp + ΔLp (CIBSE Guide B4 Formula 4.13, Table 4.36)
- Output
- dB — in-duct sound pressure level from plantroom noise breaking into the attenuator (La), per band
- Bands
- 31.5 Hz – 8 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Estimates the noise that breaks into a duct through the casing of an attenuator standing in a noisy plantroom, per CIBSE Guide B4 Formula 4.13. The plantroom's reverberant sound pressure level drives sound through the attenuator casing; the result is the in-duct level that adds to the noise downstream of the attenuator. Use it to check that the attenuator is not short-circuited by the plantroom it sits in.
Equation
- Lp — reverberant sound pressure level in the plantroom, per band.
- ΔLp — the level difference from CIBSE Table 4.36, for 1 m of unplugged attenuator with a 1.2 mm steel casing (the only case the table gives). Timbral stores it negative, so it is added. CIBSE prints the formula as La = Lp − ΔLp with ΔLp a positive loss; the result is the same.
| Band (Hz) | 31.5 | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|---|
| ΔLp (dB) | −5 | −20 | −31 | −41 | −51 | −51 | −50 | −47 | −41 |
ℹ️ No correction for attenuator length or casing thickness is applied: the table's single case is used as given.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Lp | plantroom reverberant sound pressure level (a spectrum row) | dB | see below |
Worked example
| Band (Hz) | 31.5 | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|---|
| Lp (dB) | 90 | 88 | 85 | 82 | 80 | 78 | 75 | 72 | 68 |
| La (dB) | 85 | 68 | 54 | 41 | 29 | 27 | 25 | 25 | 27 |
(e.g. at 125 Hz: 85 + (−31) = 54 dB.)
Source
CIBSE Guide B4 (2016) — Formula 4.13 (attenuator noise break-in) and Table 4.36 (level difference for an unplugged attenuator, 1.2 mm steel casing). Bands 31.5–8000 Hz.