Attenuator Noise Break-in

Formula
La = Lp + ΔLp (CIBSE Guide B4 Formula 4.13, Table 4.36)
Output
dB — in-duct sound pressure level from plantroom noise breaking into the attenuator (La), per band
Bands
31.5 Hz – 8 kHz
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Estimates the noise that breaks into a duct through the casing of an attenuator standing in a noisy plantroom, per CIBSE Guide B4 Formula 4.13. The plantroom's reverberant sound pressure level drives sound through the attenuator casing; the result is the in-duct level that adds to the noise downstream of the attenuator. Use it to check that the attenuator is not short-circuited by the plantroom it sits in.

Equation

La=Lp+ΔLpL_a = L_p + \Delta L_p
  • Lp — reverberant sound pressure level in the plantroom, per band.
  • ΔLp — the level difference from CIBSE Table 4.36, for 1 m of unplugged attenuator with a 1.2 mm steel casing (the only case the table gives). Timbral stores it negative, so it is added. CIBSE prints the formula as La = Lp − ΔLp with ΔLp a positive loss; the result is the same.
Band (Hz)31.5631252505001000200040008000
ΔLp (dB)−5−20−31−41−51−51−50−47−41

ℹ️ No correction for attenuator length or casing thickness is applied: the table's single case is used as given.

Inputs

InputMeaningUnitExample
Lpplantroom reverberant sound pressure level (a spectrum row)dBsee below

Worked example

Band (Hz)31.5631252505001000200040008000
Lp (dB)908885828078757268
La (dB)856854412927252527

(e.g. at 125 Hz: 85 + (−31) = 54 dB.)

Source

CIBSE Guide B4 (2016) — Formula 4.13 (attenuator noise break-in) and Table 4.36 (level difference for an unplugged attenuator, 1.2 mm steel casing). Bands 31.5–8000 Hz.